Dry-type power transformers

FMT Zaječar / Production programme / Railway Download this product groupPDF catalogue
Description and Application

NTSM* transformers are of dry-type design, cast in cycloaliphatic resin, insulation class "F" (maximum permissible temperature 155°C). The transformation ratio of the transformer is given in the table. They are manufactured for a rated primary voltage of 25 kV, i.e. a highest voltage for equipment of up to 52 kV.

Among their wide range of applications, we particularly highlight their use on the railway at level crossings for powering signalling equipment.

Mounting and Maintenance

By design, these transformers are primarily used in locations that require resistance to flammability, moisture, chemical influences and short circuits. The transformers are designed for outdoor mounting and, due to their construction (creepage distances >31 mm/kV), can be installed in heavily polluted environments. The transformer is connected to the supply and outgoing conductors via stainless-steel terminals.

During the operation of dry-type epoxy transformers, almost no maintenance is required. It is recommended to periodically check that the connections on the transformer terminals are secure, since vibration can cause them to loosen. The transformer should also be wiped free of dust and other contamination.

NTSM-38-1.5
NTSM-38-1.5 / NTSM-38-2.5
Dry-type power transformers

Dry-type power transformers
NTSM-38-1.5 and NTSM-38-2.5

Rated power (VA)1500Rated power (VA)2500
Transformation ratio (kV/kV)25 / 0.22Maximum operating voltage (kV)27.5
Highest voltage for equipment (kV)52Test voltage 50Hz, 1min (kV)95
Impulse test voltage 1,2/50 (kV)250Lowest continuous operating voltage (kV)19
Creepage distance (mm) / Insulation1329 mm | Cycloaliphatic resin
Weight (kg)85 kgWeight (kg)102 kg
Secondary winding contacts (V)Version 1Version 2
A-N (Primary winding)25000 V25000 V
a1-n209 V220 V
a2-n220 V231 V
a3-n231 V242 V
a4-n242 V253 V
a5-n253 V264 V
NTSM-38-5
NTSM-38-5 / NTSM-38-10
Dry-type power transformers

Dry-type power transformers
NTSM-38-5 and NTSM-38-10

Rated power (VA)5000Rated power (VA)10000
Transformation ratio (kV/kV)25 / 0.22Maximum operating voltage (kV)27.5
Highest voltage for equipment (kV)52Test voltage 50Hz, 1min (kV)95
Impulse test voltage 1,2/50 (kV)250Lowest continuous operating voltage (kV)19
Creepage distance (mm) / Insulation1332 mm | Cycloaliphatic resin
Weight (kg)132 kgWeight (kg)152 kg
Secondary winding contacts (V)Version 1Version 2
A-N (Primary winding)25000 V25000 V
a1-n209 V220 V
a2-n220 V231 V
a3-n231 V242 V
a4-n242 V253 V
a5-n253 V264 V
NTSM-38-16
NTSM-38-16 / 20 / 25
Dry-type power transformers

Dry-type power transformers
NTSM-38-16, NTSM-38-20 and NTSM-38-25

Rated power (VA)160002000025000
Transformation ratio (kV/kV)25 / 0.2225 / 0.2225 / 0.22
Maximum operating voltage (kV)27.527.527.5
Highest voltage for equipment (kV)525252
Test voltage 50Hz, 1min. (kV)959595
Impulse test voltage 1,2/50 (kV)250250250
Lowest continuous operating voltage (kV)191919
Creepage distance (mm)136613661366
Type of basic insulationCycloaliphatic resin
Weight (kg)328 kg350 kg370 kg