Medium-voltage voltage transformers

FMT Zaječar / Product range Download this product groupPDF catalogue
Application and description

APPLICATION: Instrument voltage transformers are used to isolate measuring and protection devices from high voltage and to transform the voltage to a value suitable for measuring and protection devices.

DESCRIPTION: The transformer cores are made of high-quality cold-rolled magnetic steel with an oriented crystal structure. The primary and secondary windings are cast in epoxy resin filled with quartz sand, which gives an electrically and mechanically very strong construction. A special design of the windings ensures an even distribution of impulse overvoltages along the windings and over the surface of the insulating part of the transformer. Thanks to all these properties, and despite their small dimensions, these transformers withstand power-frequency voltage tests and impulse overvoltage tests excellently.

Since the core is made of very high-quality magnetic steel (low specific losses), there is no danger of impermissible heating of the core in a single-pole transformer at the high inductions that can occur in the event of an earth fault in an unearthed network.

Single-pole insulated voltage transformers also have an auxiliary residual winding (tertiary) for connection in an open delta, intended for earth-fault protection. An ohmic resistance in the circuit of the open-delta residual windings of three single-pole insulated voltage transformers connected in star in networks with an isolated neutral point prevents the occurrence and persistence of ferroresonance, which can arise during transient operating conditions of the network.

We manufacture voltage transformers for all climatic conditions.

Selection of accuracy class and version

SELECTING THE ACCURACY CLASS: The accuracy class of a voltage transformer should be selected according to its purpose.

  • Class 0.1: for the most accurate laboratory measurements and calibrations;
  • Class 0.2: for laboratory measurements and test stations, for the most accurate power measurements in operation and for revenue metering of electricity consumption at large consumers;
  • Class 0.5: for operational voltage and power measurements, for metering electricity consumption and for supplying auxiliary relays;
  • Class 1: for cases where a high rated output is required and a higher class is not necessary.

CONSUMPTION OF CONNECTING CONDUCTORS FOR DETERMINING THE RATED OUTPUT OF INSTRUMENT TRANSFORMERS: These data should be taken into account when selecting the rated output of instrument transformers, in addition to the consumption of the measuring or protection devices being connected.

LoadPower consumption per system (W/m)
Cu conductor 1 m, 2.5 mm² at 5 A0.18
Cu conductor 1 m, 4 mm² at 5 A0.11
Cu conductor 1 m, 2.5 mm² at 1 A0.007
Cu conductor 1 m, 4 mm² at 1 A0.0044

VERSIONS: We make transformers for indoor and outdoor installation. For indoor installation there are also versions with high-voltage fuse holders that can be mounted directly on the transformer. There are also reconnectable versions, where the transformer can be used for both 10 kV and 20 kV networks by special reconnection.

Filters
Mounting
Rated primary voltage (kV)
Voltages for which transformers are made on customer request are also included.
Highest voltage for equipment (kV)
Version
Single-pole voltage transformers 12-38 kV
Medium voltage

Single-pole voltage transformers 12-38 kV

Voltage: 12 kV, 24 kV, 38 kV | Mounting: Indoor / Outdoor | Insulation: Epoxy resin

To prevent ferroresonance, when single-pole voltage transformers are used in networks with an isolated neutral, an additional resistor must be installed in the tertiary circuit (the open delta of the transformers).

For transformers for indoor mounting, the housing and fuse are ordered separately, except for the model JNT SOP* in which they are integrated.

When ordering transformers, always state the primary, secondary and tertiary voltages, accuracy class and rated output. On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

Subcategories:
JNT-12
JNT-12
Single-pole voltage transformers
JNT-12, JNT-24, JNT-24/12, JNT-36

Mounting: Indoor | Highest voltage for equipment: 12; 24; 36; 38 kV | Single-pole

We can also make these transformers for rated primary voltages: 3/√3; 5/√3; 6/√3; 15/√3; 17.5/√3; 25/√3 and 33/√3 kV.

TECHNICAL DATAJNT-12JNT-24JNT-24/12JNT-36
Rated primary voltage (kV)10/√320/√320/√3//10/√335/√3
Highest voltage for equipment (r.m.s.) (kV)12242438 (36)
Rated secondary voltage (V)100/√3 or 110/√3
Rated tertiary voltage (V)100/3 or 110/3
Rated power-frequency withstand voltage (kV)28505070
Rated impulse voltage 1.2/50 µs (kV)75125125170
Rated frequency (Hz)50/60
Maximum rated output for accuracy class 0.2 (VA)253030/1030
Maximum rated output for accuracy class 0.5 (VA)757575/25100
Maximum rated output for accuracy class 1 (VA)150150150/50200
Rated tertiary output (VA)25; 50; 100
Rated tertiary accuracy class3P; 6P
Rated voltage factor1.9/8h
Additional resistance in the tertiary circuit (Ω)25252516.5
Thermal limiting output (VA)600600600/300800
Mass (kg)24.631.532.541
Insulation temperature classE/B
Type of main insulationEpoxy resin
Applicable standardsIEC 61869-1; IEC 61869-3
Dimensions (mm)
Transformer typeDimensions (mm)
ABCDEFG
JNT-123551802451901559372
JNT-243752002982101759372
JNT-24/123752002982101759372
JNT-3638522538924520074.565.5
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary, secondary and tertiary voltages, accuracy class and rated output. We reserve the right to make changes.

JNT SOP-24
JNT SOP-24
Single-pole voltage transformers with integrated housing
JNT SOP-12, JNT SOP-24, JNT SOP-24/12

Mounting: Indoor | Highest voltage for equipment: 12; 24 kV | Single-pole | Integrated fuse housing in the primary

JNT SOP transformers are suitable for installation in smaller cubicles up to the 24 kV voltage level. They have fuse housings on the high-voltage side, and with the transformer we supply the appropriate fuse cartridges, which are extremely easy to fit and remove.

We can also make these transformers for primary voltages: 3/√3; 5/√3; 6/√3; 11/√3; 15/√3 and 22/√3 kV.

TECHNICAL DATAJNT SOP-12JNT SOP-24JNT SOP-24/12
Rated primary voltage (kV)10/√320/√320/√3//10/√3
Highest voltage for equipment (r.m.s.) (kV)122424
Rated secondary voltage (V)100/√3 or 110/√3
Rated tertiary voltage (V)100/3 or 110/3
Rated power-frequency withstand voltage (kV)285050
Rated impulse voltage 1.2/50 µs (kV)75125125
Rated frequency (Hz)50/60
Maximum rated output for accuracy class 0.2 (VA)253030/10
Maximum rated output for accuracy class 0.5 (VA)757575/25
Maximum rated output for accuracy class 1 (VA)150150150/50
Rated tertiary output (VA)25; 50; 100
Rated tertiary accuracy class3P; 6P
Rated voltage factor1.9/8h
Additional resistance in the tertiary circuit (Ω)25
Thermal limiting output (VA)600600600/300
Mass (kg)232930.5
Insulation temperature classE/B
Type of main insulationEpoxy resin
Applicable standardsIEC 61869-1; IEC 61869-3
Dimensions (mm)
Transformer typeDimensions (mm)
ABCDEFGH
JNT SOP-12533240280353270125312148
JNT SOP-24606300340416275130325178
JNT SOP-24/12606300340416275130325178
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary, secondary and tertiary voltages, accuracy class and rated output. We reserve the right to make changes.

JNT-10
JNT-10
Single-pole voltage transformers of reduced dimensions
JNT-10, JNT-10U, JNT-20U, JNT-30U

Mounting: Indoor | Highest voltage for equipment: 12; 24; 36; 42 kV | Single-pole

We can also make these transformers for rated primary voltages: 3/√3; 5/√3; 6/√3; 15/√3; 17.5/√3; 25/√3 and 33/√3 kV.

TECHNICAL DATAJNT-10JNT-10UJNT-20UJNT-30U
Rated primary voltage (kV)10/√310/√320/√335/√3
Highest voltage for equipment (r.m.s.) (kV)12122436 (42)
Rated secondary voltage (V)100/√3 or 110/√3
Rated tertiary voltage (V)100/3 or 110/3
Rated power-frequency withstand voltage (kV)2828 (42)50 (65)70 (95)
Rated impulse voltage 1.2/50 µs (kV)7575125170 (190)
Rated frequency (Hz)50/60
Maximum rated output for accuracy class 0.2 (VA)15303030
Maximum rated output for accuracy class 0.5 (VA)50757575
Maximum rated output for accuracy class 1 (VA)100150150150
Rated tertiary output (VA)25; 50; 10010-5010-5010-50
Rated tertiary accuracy class3P; 6P3P; 6P3P; 6P3P; 6P
Rated voltage factor1.9/8h1.9/8h1.9/8h1.9/8h
Additional resistance in the tertiary circuit (Ω)25252525
Thermal limiting output (VA)400600600800
Mass (kg)17304360
Insulation temperature classE/B
Type of main insulationEpoxy resin
Applicable standardsIEC 61869-1; IEC 61869-3IEC 61869-1; IEC 61869-3; GOST 1983
Dimensions (mm)
Transformer typeDimensions (mm)
ABCDEFGIJ
JNT-103201482372101158119M811
JNT-10U2752202512151803030M1013
JNT-20U31524229024020737.537.5M1013
JNT-30U4152503903002259025M1013
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary, secondary and tertiary voltages, accuracy class and rated output. We reserve the right to make changes.

JNTm2-24
JNTm2-24
Single-pole voltage transformers of reduced dimensions
JNT-10d, JNTm2-24, JNTm2-24/12

Mounting: Indoor | Highest voltage for equipment: 12; 24 kV | Single-pole

We can also make these transformers for primary voltages: 3/√3; 5/√3; 6/√3; 11/√3; 15/√3 and 22/√3 kV.

TECHNICAL DATAJNT-10dJNTm2-24JNTm2-24/12
Rated primary voltage (kV)10/√320/√320/√3//10/√3
Highest voltage for equipment (r.m.s.) (kV)122424
Rated secondary voltage (V)100/√3 or 110/√3
Rated tertiary voltage (V)100/3 or 110/3
Rated power-frequency withstand voltage (kV)285050
Rated impulse voltage 1.2/50 µs (kV)75125125
Rated frequency (Hz)50/60
Maximum rated output for accuracy class 0.2 (VA)1515-
Maximum rated output for accuracy class 0.5 (VA)505050/15
Maximum rated output for accuracy class 1 (VA)10010075/25
Rated tertiary output (VA)25; 50; 100
Rated tertiary accuracy class3P; 6P
Rated voltage factor1.9/8h
Additional resistance in the tertiary circuit (Ω)252525
Thermal limiting output (VA)400400400/200
Mass (kg)212727
Insulation temperature classE/B
Type of main insulationEpoxy resin
Applicable standardsIEC 61869-1; IEC 61869-3
Dimensions (mm)
Transformer typeDimensions (mm)
ABCDEFGIJ
JNT-10d3401482202701255317M1011
JNTm2-243551782712801505322M1014
JNTm2-24/123551782712801505322M1014
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary, secondary and tertiary voltages, accuracy class and rated output. We reserve the right to make changes.

REL 20
REL 20
Single-pole voltage transformers of reduced dimensions - BLOCK TYPE
REL 10, REL 20, REL 20/10

Mounting: Indoor | Highest voltage for equipment: 12; 24 kV | Single-pole | Block type

We can also make these transformers for primary voltages: 3/√3; 5/√3; 6/√3; 11/√3; 15/√3 and 22/√3 kV.

TECHNICAL DATAREL 10REL 20REL 20/10
Rated primary voltage (kV)10/√320/√320/√3//10/√3
Highest voltage for equipment (r.m.s.) (kV)122424
Rated secondary voltage (V)100/√3 or 110/√3
Rated tertiary voltage (V)100/3 or 110/3
Rated power-frequency withstand voltage (kV)28 (42)50 (65)50 (65)
Rated impulse voltage 1.2/50 µs (kV)75125125
Rated frequency (Hz)50/60
Maximum rated output for accuracy class 0.2 (VA)151510(5)
Maximum rated output for accuracy class 0.5 (VA)505030(15)
Maximum rated output for accuracy class 1 (VA)100120120(50)
Rated tertiary output (VA)10-50
Rated tertiary accuracy class3P; 6P
Rated voltage factor1.9/8h
Additional resistance in the tertiary circuit (Ω)50
Thermal limiting output (VA)400400400/200
Insulation temperature classE
Type of main insulationEpoxy resin
Applicable standardsIEC 61869-1; IEC 61869-3 (GOST 1983)
Dimensions (mm)
Transformer typeDimensions (mm)Mass (kg)
ABCDEFG
REL 103251482001252601511~18.5
REL 203511782301502752014~25
REL 20/103511782301502752014~25
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary, secondary and tertiary voltages, accuracy class and rated output. We reserve the right to make changes.

JNT-12z
JNT-12z
Single-pole voltage transformers of reduced dimensions - BLOCK TYPE
JNT-12z, JNT-12d, JNT-24z, JNT-24d, JNT-24/12z, JNT-24/12d

Mounting: Indoor | Highest voltage for equipment: 12; 24 kV | Single-pole | Block type

We can also make these transformers for primary voltages: 3/√3; 5/√3; 6/√3; 11/√3; 15/√3 and 22/√3 kV.

TECHNICAL DATAJNT-12zJNT-12dJNT-24zJNT-24dJNT-24/12zJNT-24/12d
Rated primary voltage (kV)10/√310/√320/√320/√320/√3//10/√320/√3//10/√3
Highest voltage for equipment (r.m.s.) (kV)121224242424
Rated secondary voltage (V)100/√3 or 110/√3
Rated tertiary voltage (V)100/3 or 110/3
Rated power-frequency withstand voltage (kV)282850505050
Rated impulse voltage 1.2/50 µs (kV)7575125125125125
Rated frequency (Hz)50/60
Maximum rated output for accuracy class 0.2 (VA)2525303030/1030/10
Maximum rated output for accuracy class 0.5 (VA)7575757575/2575/25
Maximum rated output for accuracy class 1 (VA)150150150150150/50150/50
Rated tertiary output (VA)25; 50; 100
Rated tertiary accuracy class3P; 6P
Rated voltage factor1.9/8h
Additional resistance in the tertiary circuit (Ω)252525252525
Thermal limiting output (VA)500600600700600/300700/350
Mass (kg)24.624.631.53332.534.5
Insulation temperature classE/B
Type of main insulationEpoxy resin
Applicable standardsIEC 61869-1; IEC 61869-3; DIN 42600-9
Dimensions (mm)
Transformer typeDimensions (mm)
ABCDEFGHIKJ
JNT-12z3481482342701254815152150183Ø12, Ø14
JNT-12d3581482342751255515162150195Ø12, Ø14
JNT-24z3681782932801505320162160193Ø12, Ø14
JNT-24d3921782932751507032174172205Ø12, Ø14
JNT-24/12z3681782932801505320162160193Ø12, Ø14
JNT-24/12d3921782932751507032174172205Ø12, Ø14
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary, secondary and tertiary voltages, accuracy class and rated output. We reserve the right to make changes.

JNT-38z
JNT-38z
Single-pole voltage transformers of reduced dimensions - BLOCK TYPE
JNT-38z, JNT-38d, JNT-36d

Mounting: Indoor | Highest voltage for equipment: 36; 38; 40.5 kV | Single-pole | Block type

We can also make these transformers for primary voltages: 3/√3; 5/√3; 6/√3; 11/√3; 15/√3; 22/√3 and 30/√3 kV.

TECHNICAL DATAJNT-38zJNT-38dJNT-36d
Rated primary voltage (kV)35/√335/√335/√3
Highest voltage for equipment (r.m.s.) (kV)3838 (40.5)36, 38 (40.5)
Rated secondary voltage (V)100/√3 or 110/√3
Rated tertiary voltage (V)100/3 or 110/3
Rated power-frequency withstand voltage (kV)7070 (80)70 (80)
Rated impulse voltage 1.2/50 µs (kV)170170 (190)170 (190)
Rated frequency (Hz)50/60
Maximum rated output for accuracy class 0.2 (VA)253050
Maximum rated output for accuracy class 0.5 (VA)75100150
Maximum rated output for accuracy class 1 (VA)150200300
Rated tertiary output (VA)25; 50; 10025; 50; 100; 150
Rated tertiary accuracy class3P; 6P
Rated voltage factor1.9/8h
Additional resistance in the tertiary circuit (Ω)2525 (16.7)16.7 (12.5)
Thermal limiting output (VA)6008001200
Mass (kg)344072
Insulation temperature classE/B
Type of main insulationEpoxy resin
Applicable standardsIEC 61869-1; IEC 61869-3
Dimensions (mm)
Transformer typeDimensions (mm)
ABCDFGHIK
JNT-38z36821034224570.537.5162160193
JNT-38d39222038424582.549.5174172205
JNT-36d4432403763008840207190238
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary, secondary and tertiary voltages, accuracy class and rated output. We reserve the right to make changes.

JNT SM-12
JNT SM-12
Single-pole voltage transformers for outdoor mounting
JNT SM-12, JNT SM-24, JNT SM-24/12, JNT SM-36*

Mounting: Outdoor | Highest voltage for equipment: 12; 24; 36; 38 kV | Single-pole

We can also make these transformers for primary voltages: 3/√3; 5/√3; 6/√3; 11/√3; 15/√3; 22/√3 and 30/√3 kV.

TECHNICAL DATAJNT SM-12JNT SM-24JNT SM-24/12JNT SM-36*
Rated primary voltage (kV)10/√320/√320/√3//10/√335/√3
Highest voltage for equipment (r.m.s.) (kV)12242438 (36)
Rated secondary voltage (V)100/√3 or 110/√3
Rated tertiary voltage (V)100/3 or 110/3
Rated power-frequency withstand voltage (kV)28505070
Rated impulse voltage 1.2/50 µs (kV)75125125170
Rated frequency (Hz)50/60
Maximum rated output for accuracy class 0.2 (VA)253030/1030
Maximum rated output for accuracy class 0.5 (VA)757575/25100
Maximum rated output for accuracy class 1 (VA)150150150/50200
Rated tertiary output (VA)25; 50; 100
Rated tertiary accuracy class3P; 6P
Rated voltage factor1.9/8h
Additional resistance in the tertiary circuit (Ω)25252516.5
Thermal limiting output (VA)600600600/300800
Mass (kg)25.931.532.543
Insulation temperature classE/B
Type of main insulationEpoxy resin
Applicable standardsIEC 61869-1; IEC 61869-3
Dimensions (mm)
Transformer typeDimensions (mm)Number of shedsCreepage distance (mm)
ABCDEFG
JNT SM-1236619036720916598213500
JNT SM-2437019044722016590.527.54630
JNT SM-24/1237019044722016590.527.54630
JNT SM-36-5R37922554922920092255855
JNT SM-36-6R37922557922920092256920
JNT SM-36-8R379225626229200922581125
JNT SM-36-10R3792256952292009225101280
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

* - applies to all models of that type (JNT SM-36-5R, JNT SM-36-6R, JNT SM-36-8R, JNT SM-36-10R).

When ordering, always state the primary, secondary and tertiary voltages, accuracy class and rated output. We reserve the right to make changes.

NTSM-38
NTSM-38
Single-pole voltage transformers for outdoor mounting 12-42 kV
NTSM-12, NTSM-24, NTSM-38

Mounting: Outdoor | Highest voltage for equipment: 12; 24; 36; 42 kV | Single-pole | Cycloaliphatic resin

We can also make these transformers for primary voltages: 3/√3; 5/√3; 6/√3; 11/√3; 15/√3; 22/√3 and 30/√3 kV.

TECHNICAL DATANTSM-12NTSM-24NTSM-38
Rated primary voltage (kV)10/√320/√335/√3
Highest voltage for equipment (r.m.s.) (kV)122436 (42)
Rated secondary voltage (V)100/√3 or 110/√3
Rated tertiary voltage (V)100/3 or 110/3
Rated power-frequency withstand voltage (kV)28 (42)50 (65)70 (95)
Rated impulse voltage 1.2/50 µs (kV)75125170 (190)
Rated frequency (Hz)50/60
Maximum rated output for accuracy class 0.2 (VA)151520
Maximum rated output for accuracy class 0.5 (VA)505075
Maximum rated output for accuracy class 1 (VA)100120150
Rated tertiary output (VA)10-50
Rated tertiary accuracy class3P; 6P
Rated voltage factor1.9/8h
Additional resistance in the tertiary circuit (Ω)25-50
Thermal limiting output (VA)600
Insulation temperature classF
Type of main insulationCycloaliphatic resin
Applicable standardsIEC 61869-1; IEC 61869-3 (GOST 1983)
Dimensions (mm)
Transformer typeDimensions (mm)Mass (kg)
ABCDEFGI
NTSM-12315372Pg1628027622422414~40
NTSM-24315450Pg1628027622422414~58
NTSM-38315520Pg1628027622422414~72
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary, secondary and tertiary voltages, accuracy class and rated output. We reserve the right to make changes.

JNT SM-10
JNT SM-10
Single-pole voltage transformers of reduced rated output
JNT SM-10

Mounting: Outdoor | Highest voltage for equipment: 12 kV | Single-pole

We can also make these transformers for primary voltages: 3/√3; 5/√3; 6/√3 and 11/√3 kV.

TECHNICAL DATAJNT SM-10
Rated primary voltage (kV)10/√3
Highest voltage for equipment (r.m.s.) (kV)12
Rated secondary voltage (V)100/√3 or 110/√3
Rated tertiary voltage (V)100/3 or 110/3
Rated power-frequency withstand voltage (kV)28
Rated impulse voltage 1.2/50 µs (kV)75
Rated frequency (Hz)50/60
Maximum rated output for accuracy class 0.2 (VA)15
Maximum rated output for accuracy class 0.5 (VA)50
Maximum rated output for accuracy class 1 (VA)100
Rated tertiary output (VA)25; 50; 100
Rated tertiary accuracy class3P; 6P
Rated voltage factor1.9/8h
Additional resistance in the tertiary circuit (Ω)25
Thermal limiting output (VA)400
Creepage distance (mm)465
Mass (kg)18.2
Insulation temperature classE/B
Type of main insulationEpoxy resin
Applicable standardsIEC 61869-1; IEC 61869-3
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary, secondary and tertiary voltages, accuracy class and rated output. We reserve the right to make changes.

JNTm2 SM-24
JNTm2 SM-24
Single-pole voltage transformers of reduced rated output
JNTm2 SM-24, JNTm2 SM-24/12

Mounting: Outdoor | Highest voltage for equipment: 24 kV | Single-pole

We can also make these transformers for primary voltages: 3/√3; 5/√3; 6/√3; 11/√3; 15/√3 and 22/√3 kV.

TECHNICAL DATAJNTm2 SM-24JNTm2 SM-24/12
Rated primary voltage (kV)20/√320/√3//10/√3
Highest voltage for equipment (r.m.s.) (kV)24
Rated secondary voltage (V)100/√3 or 110/√3
Rated tertiary voltage (V)100/3 or 110/3
Rated power-frequency withstand voltage (kV)50
Rated impulse voltage 1.2/50 µs (kV)125
Rated frequency (Hz)50/60
Maximum rated output for accuracy class 0.2 (VA)15-
Maximum rated output for accuracy class 0.5 (VA)5050/15
Maximum rated output for accuracy class 1 (VA)10075/25
Rated tertiary output (VA)25; 50; 100
Rated tertiary accuracy class3P; 6P
Rated voltage factor1.9/8h
Additional resistance in the tertiary circuit (Ω)25
Thermal limiting output (VA)400400/200
Creepage distance (mm)535
Mass (kg)27.528
Insulation temperature classE/B
Type of main insulationEpoxy resin
Applicable standardsIEC 61869-1; IEC 61869-3
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary, secondary and tertiary voltages, accuracy class and rated output. We reserve the right to make changes.

Double-pole voltage transformers 12-38 kV
Medium voltage

Double-pole voltage transformers 12-38 kV

Voltage: 12 kV, 24 kV, 38 kV | Mounting: Indoor / Outdoor | Insulation: Epoxy resin

When ordering, always state the primary and secondary voltages, accuracy class and rated output.

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

Subcategories:
Indoor mounting - Auxiliary power transformers
Voltage: 7.2 kV, 12 kV, 17.5 kV, 24 kV, 36 kV | Double-pole | Epoxy resin
DNT-24E
DNT-24E
Double-pole auxiliary power transformers
DNT-24E

Mounting: Indoor | Highest voltage for equipment: 7.2; 12; 17.5; 24 kV | Double-pole | Auxiliary power transformer

We can also make these transformers for primary voltages: 3; 5; 6; 15; 17.5 and 22 kV.

Important warning

During installation, pay attention to the connections according to these instructions.

Incorrect connection can cause damage to the transformer and injury.

Terminal "a" MUST NOT be connected to earth - THIS CAUSES A SHORT CIRCUIT AND DAMAGE to the transformer if terminal "b" in the secondary terminal box is connected to the base with an M5x20 screw at point 2.

TECHNICAL DATADNT-24E
Rated primary voltage (kV)6101520
Highest voltage for equipment (r.m.s.) (kV)7.21217.524
Rated secondary voltage (V)220 or 230
Rated power-frequency withstand voltage, 1 min (kV)20283850
Rated impulse voltage 1.2/50 µs (kV)607595125
Rated frequency (Hz)50/60
Thermal limiting output (VA)2500250020002000
Rated voltage factor Vf1.2 continuous
Mass (kg)38.5394040
Insulation temperature classE/B
Type of main insulationEpoxy resin
Applicable standardsIEC 60076-1; IEC 61869-1; IEC 61869-3
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary and secondary voltages, accuracy class and rated output. We reserve the right to make changes.

DNT-36
DNT-36
Double-pole auxiliary power transformers
DNT-36

Mounting: Indoor | Highest voltage for equipment: 7.2; 12; 24; 36 kV | Double-pole | Auxiliary power transformer

We can also make these transformers for primary voltages: 3; 5; 6; 15; 17.5; 25 and 33 kV.

TECHNICAL DATADNT-36
Rated primary voltage (kV)6102035
Highest voltage for equipment (r.m.s.) (kV)7.2122436
Rated secondary voltage (V)220 or 230
Rated power-frequency withstand voltage, 1 min (kV)20285070
Rated impulse voltage 1.2/50 µs (kV)6075125170
Rated frequency (Hz)50/60
Thermal limiting output (VA)5000500040002500
Rated voltage factor Vf1.2 continuous
Mass (kg)58.5596264
Insulation temperature classE/B
Type of main insulationEpoxy resin
Applicable standardsIEC 60076-1; IEC 61869-1; IEC 61869-3
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary and secondary voltages, accuracy class and rated output. We reserve the right to make changes.

DNT-12
DNT-12
Double-pole voltage transformers
DNT-12, DNTm1-24, DNT-24, DNT-24/12, DNT-36

Mounting: Indoor | Highest voltage for equipment: 12; 24; 36; 38 kV | Double-pole

We can also make these transformers for primary voltages: 3; 4; 6; 11; 15; 22 and 30 kV.

The DNTm1-24 voltage transformer is a version with reduced rated output and smaller dimensions, which makes it suitable for smaller cubicles.

TECHNICAL DATADNT-12DNTm1-24DNT-24DNT-24/12DNT-36
Rated primary voltage (kV)10202020/1035
Highest voltage for equipment (r.m.s.) (kV)1224242438 (36)
Rated secondary voltage (V)100 or 110
Rated power-frequency withstand voltage (kV)2850505070
Rated impulse voltage 1.2/50 µs (kV)75125125125170
Rated frequency (Hz)50/60
Maximum rated output for accuracy class 0.2 (VA)25153030/1030
Maximum rated output for accuracy class 0.5 (VA)75507575/25100
Maximum rated output for accuracy class 1 (VA)150100150150/50200
Rated voltage factor1.2 / continuous
Thermal limiting output (VA)600400600600/300800
Mass (kg)27.42834.535.558
Insulation temperature classE/B
Type of main insulationEpoxy resin
Applicable standardsIEC 61869-1; IEC 61869-3
Dimensions (mm)
Transformer typeDimensions (mm)
ABCDEFGHI
DNT-123551802461901559372150198
DNTm1-243551803001901559372210246
DNT-243752003002101759372210246
DNT-24/123752003002101759372210246
DNT-364302503973002257654320364
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary and secondary voltages, accuracy class and rated output. We reserve the right to make changes.

RZL 10
RZL 10
Double-pole voltage transformers of reduced dimensions - BLOCK TYPE
RZL 10, RZL 20, RZL 20/10

Mounting: Indoor | Highest voltage for equipment: 12; 24 kV | Double-pole | Block type

We can also make these transformers for primary voltages: 3; 5; 6; 11; 15 and 22 kV.

TECHNICAL DATARZL 10RZL 20RZL 20/10
Rated primary voltage (kV)102020/10
Highest voltage for equipment (r.m.s.) (kV)1224
Rated secondary voltage (V)100; 110 or 230
Rated power-frequency withstand voltage (kV)28 (42)50 (65)
Rated impulse voltage 1.2/50 µs (kV)75125
Rated frequency (Hz)50/60
Maximum rated output for accuracy class 0.2 (VA)101510(5)
Maximum rated output for accuracy class 0.5 (VA)305030(15)
Maximum rated output for accuracy class 1 (VA)100120120(50)
Rated voltage factor1.2 / continuous
Thermal limiting output (VA)400
Insulation temperature classE
Type of main insulationEpoxy resin
Applicable standardsIEC 61869-1; IEC 61869-3 (GOST 1983)
Dimensions (mm)
Transformer typeDimensions (mm)Mass (kg)
ABCDEFGHO
RZL 103251482001252601511102110~18.5
RZL 203511782301502752014165130~25
RZL 20/103511782301502752014165130~26
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary and secondary voltages, accuracy class and rated output. We reserve the right to make changes.

DNT SM-12
DNT SM-12
Double-pole voltage transformers for outdoor mounting
DNT SM-17.5, DNT SM-24, DNT SM-24/12,
DNT SM-36, DNT SM-36S, DNT SM-36-8R, DNT SM-36-10R

Mounting: Outdoor | Highest voltage for equipment: 12; 17.5; 24; 38; 40.5 kV | Double-pole

We can also make these transformers for primary voltages: 3; 5; 6.3; 11; 15; 22 and 30 kV.

TECHNICAL DATADNT SM-17.5DNT SM-24DNT SM-24/12DNT SM-36DNT SM-36SDNT SM-36-8RDNT SM-36-10R
Rated primary voltage (kV)15 (10)2020/1035353535
Highest voltage for equipment (r.m.s.) (kV)17.5 (12)2424383840.540.5
Rated secondary voltage (V)100 or 110
Rated power-frequency withstand voltage (kV)38 (28)505070708080
Rated impulse voltage 1.2/50 µs (kV)95 (75)125125170170190190
Rated frequency (Hz)50/60
Maximum rated output for accuracy class 0.2 (VA)253030/1030303030
Maximum rated output for accuracy class 0.5 (VA)757575/25100100100100
Maximum rated output for accuracy class 1 (VA)150150150/50200200200200
Rated voltage factor1.2 / continuous
Thermal limiting output (VA)600600600/300800800800-1200800-1200
Mass (kg)27.6363760536366
Insulation temperature classE/B
Type of main insulationEpoxy resin
Applicable standardsIEC 61869-1; IEC 61869-3
Dimensions (mm)
Transformer typeDimensions (mm)Number of shedsCreepage distance (mm)
ABCDEFGHI
DNT SM-17.536019036720716594282102923500
DNT SM-2437319044922016594313204064650
DNT SM-24/1237319044922016594313204064650
DNT SM-3642522555127020096334305205900
DNT SM-36S41022550626020091284305156900
DNT SM-36-8R425225613270200963349057381152
DNT SM-36-10R4252256762702009633536613101320
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary and secondary voltages, accuracy class and rated output. We reserve the right to make changes.

NTDSM-24
NTDSM-24
Double-pole voltage transformers for outdoor mounting 12-24 kV
NTDSM-12, NTDSM-24, NTDSM-24/12

Mounting: Outdoor | Highest voltage for equipment: 12; 24 kV | Double-pole | Cycloaliphatic resin

We can also make these transformers for primary voltages: 3; 5; 6; 11; 15 and 22 kV.

TECHNICAL DATANTDSM-12NTDSM-24NTDSM-24/12
Rated primary voltage (kV)102020/10
Highest voltage for equipment (r.m.s.) (kV)1224
Rated secondary voltage (V)100; 110 or 230
Rated power-frequency withstand voltage (kV)28 (42)50 (65)
Rated impulse voltage 1.2/50 µs (kV)75125
Rated frequency (Hz)50/60
Maximum rated output for accuracy class 0.2 (VA)151510(5)
Maximum rated output for accuracy class 0.5 (VA)757530(15)
Maximum rated output for accuracy class 1 (VA)150150120(50)
Rated voltage factor1.2 / continuous
Thermal limiting output (VA)600
Insulation temperature classF
Type of main insulationCycloaliphatic resin
Applicable standardsIEC 61869-1; IEC 61869-3 (GOST 1983)
Dimensions (mm)
Transformer typeDimensions (mm)Mass (kg)
ABCDEFGHIOR
NTDSM-1232022031537030327018321527.51325~32
NTDSM-24350242430449368300207240301325~48
NTDSM-24/12350242430449368300207240301325~49
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary and secondary voltages, accuracy class and rated output. We reserve the right to make changes.

NTDSM-0.63-12
NTDSM-0.63-12
Double-pole voltage transformers for outdoor mounting 12-24 kV
NTDSM-0.63-12, NTDSM-1.25-12,
NTDSM-0.63-24, NTDSM-1.25-24

Mounting: Outdoor | Highest voltage for equipment: 12; 24 kV | Double-pole | Cycloaliphatic resin

We can also make these transformers for primary voltages: 3; 5; 6; 11; 15 and 22 kV.

TECHNICAL DATANTDSM-0.63-12NTDSM-1.25-12NTDSM-0.63-24NTDSM-1.25-24
Rated primary voltage (kV)3; 6; 1010; 15; 20
Highest voltage for equipment (r.m.s.) (kV)1224
Rated secondary voltage (V)218; 224; 230; 236; 242
Rated power-frequency withstand voltage (kV)2850
Rated impulse voltage 1.2/50 µs (kV)75125
Rated frequency (Hz)50/60
Rated output (VA)6301250
No-load losses (W)5050
Short-circuit voltage (%)4.54.5±10
Load losses (W)5550
Rated voltage factor1.2 / continuous
Insulation temperature classE
Type of main insulationCycloaliphatic resin
Applicable standardsIEC 61869-1; IEC 61869-3 (GOST 1983)
Dimensions (mm)
Transformer typeDimensions (mm)Mass (kg)
ABCDEFGHIOR
NTDSM-0.63-1232022031537030327018321527.51325~32
NTDSM-1.25-1232022031537030327018321527.51325~34
NTDSM-0.63-24350242430449368300207240301325~48
NTDSM-1.25-24350242430449368300207240301325~50
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary and secondary voltages, accuracy class and rated output. We reserve the right to make changes.

NTDSM-24h
NTDSM-24h
Double-pole voltage transformers for outdoor mounting
NTDSM-24h, NTDSM-24/12h

Mounting: Outdoor | Highest voltage for equipment: 24 kV | Double-pole

We can also make these transformers for primary voltages: 3; 5; 6; 6.3; 11; 15 and 22 kV.

TECHNICAL DATANTDSM-24hNTDSM-24/12h
Rated primary voltage (kV)2020/10
Highest voltage for equipment (r.m.s.) (kV)2424
Rated secondary voltage (V)100; 110 or 230
Rated power-frequency withstand voltage (kV)5050
Rated impulse voltage 1.2/50 µs (kV)125125
Rated frequency (Hz)50/60
Maximum rated output for accuracy class 0.2 (VA)3030/10
Maximum rated output for accuracy class 0.5 (VA)7575/25
Maximum rated output for accuracy class 1 (VA)150150/50
Rated voltage factor1.2 / continuous
Thermal limiting output (VA)600600/300
Mass (kg)3637
Insulation temperature classE/B
Type of main insulationEpoxy resin
Applicable standardsIEC 61869-1; IEC 61869-3
Note

On customer request, we can also make other combinations of rated transformation ratios, accuracy classes, rated outputs and voltage factors.

When ordering, always state the primary and secondary voltages, accuracy class and rated output. We reserve the right to make changes.

Accessories for voltage transformers
Medium voltage

Accessories for voltage transformers

Residual winding resistors / High-voltage fuse housings

Resistors for suppressing ferroresonance in the open-delta (tertiary) circuit of single-pole voltage transformers, and high-voltage fuse housings for mounting on voltage transformers.

Subcategories:
ORN-25/400
ORN-25/400
Ferroresonance suppression resistor for indoor mounting
ORN-25/400, ORN-16.7/600

Mounting: Indoor | Residual (tertiary) winding resistor | For 10, 20 and 35 kV voltage transformers

To prevent ferroresonance, when single-pole voltage transformers are used in networks with an isolated neutral, a 25 Ω (400 W) resistor must be installed in the open-delta circuit for 10 and 20 kV transformers, and a 16-20 Ω (600 W) resistor for 35 kV transformers. This significantly reduces the risk of ferroresonance.

Resistor typeFor FMT voltage transformersPowerResistanceL (mm)A (mm)
ORN-25/40010 and 20 kV400 W25 Ω322305
ORN-16.7/60035 kV600 W16.7 Ω432415
ORN SM-25/400
ORN SM-25/400
Ferroresonance suppression resistor for outdoor mounting
ORN SM-25/400, ORN SM-16.7/600

Mounting: Outdoor | Residual (tertiary) winding resistor | For 10, 20 and 35 kV voltage transformers

To prevent ferroresonance, when single-pole voltage transformers are used in networks with an isolated neutral, a 25 Ω; 400 W resistor must be installed in the open-delta circuit for 10 and 20 kV transformers, and a (16-20) Ω; 600 W resistor for 35 kV transformers. This significantly reduces the risk of ferroresonance.

These resistors are always installed as standard, without the need to specify them, in the medium-voltage three-system metering units manufactured by FMT.

Resistor typeFor FMT voltage transformersPowerResistanceL (mm)A (mm)
ORN SM-25/40010 and 20 kV400 W25 Ω290210
ORN SM-16.7/60035 kV600 W16.7 Ω400320

The cable length is 2 m, or according to customer request.

FT-12
FT-12
High-voltage fuse housings
FT-12, FT-24, FT-36

Mounting on the voltage transformer: vertical or horizontal | For 10, 20 and 35 kV networks

FT fuse housings can be mounted on the voltage transformer in a vertical or horizontal position using an adapter that we supply.

On special customer request, the housings are supplied with or without fuse cartridges.

Housing typeRated voltage (kV)A (mm)B (mm)Fuse dimensions (mm)Mass of housing without fuse (kg)
FT-1210179137Ø60x1600.8
FT-2420284242Ø60x2651.06
FT-3635380338Ø60x3581.44
KO VVC36kV
KO VVC36kV
High-voltage fuse housings
KO VVC12kV, KO VVC24kV, KO VVC36kV (VVC-*)

Mounting on the voltage transformer: vertical only | For 10, 20 and 35 kV networks

VVC fuse housings can be mounted on the voltage transformer in a vertical position only.

On special customer request, the housings are supplied with or without fuse cartridges.

Housing typeRated voltage (kV)A (mm)H (mm)Fuse dimensions (mm)Mass of housing without fuse (kg)
KO VVC12kV10314339Ø53x1921.93
KO VVC24kV20414439Ø53x2922.33
KO VVC36kV35564589Ø53x4422.88
Examples of fuse housings mounted on voltage transformers

Fuse housing mounted vertically (VVC and FT) and horizontally (FT)

Example of a fuse housing mounted on a voltage transformer 1
Example of a fuse housing mounted on a voltage transformer 2
Example of a fuse housing mounted on a voltage transformer 3